EasyManua.ls Logo

Woodward GCP-30 Series - Page 45

Woodward GCP-30 Series
179 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37365A GCP-30 Series Packages - Genset Control
© Woodward Page 45/179
Analog Controller (BPQ, XPQ: Setting 'ANALOG')
Parameter 61
V/Q contr.output
----------------
BPQ, XPQ
Voltage controller: range see below
If "V/Q contr.type" (Parameter 57) has been configured as "ANALOG", this para-
meter must be configured to the appropriate type of analog controller signal. The
range of the analog output is configured here. To switch from a current to a voltage
signal output, a jumper must be installed between terminals 11/12. The available
ranges are listed below.
Type Setting in above
configuration
screen
Jumper
between
term. 11/12
Range
Lower
level
Upper
level
Current +/-20mA (+/-10V) no +/-20mA -20 mA +20 mA
+/-10mA (+/-5V) +/-10mA -10 mA +20 mA
0 to 10mA (0 to 5V) 0-10mA 0 mA 10 mA
0 to 20mA (0 to 10V) 0-20mA 0 mA 20 mA
4 to 20mA 4-20mA 4 mA 20 mA
10 to 0mA (5 to 0V) 10-0mA 10 mA 0 mA
20 to 0mA (10 to 0V) 20-0mA 20 mA 0 mA
20 to 4mA 20-4mA 20 mA 4 mA
Voltage +/-20mA (+/-10V) yes +/-10V -10 Vdc +10 Vdc
+/-10mA (+/-5V) +/-5V -5 Vdc +5 Vdc
+/-3V +/-3V -3 Vdc +3 Vdc
+/-2.5V +/-2.5V -2.5Vdc +2.5 Vdc
+/-1V +/-1V -1 Vdc +1 Vdc
0 to 10mA (0 to 5V) 0 to 5V 0 Vdc 5 Vdc
0.5V to 4.5V 0.5 to 4.5V 0.5 Vdc 4.5 Vdc
0 to 20mA (0 to 10V) 0 to 10V 0 Vdc 10 Vdc
10 to 0mA (5 to 0V) 5 to 0V 5 Vdc 0 Vdc
4.5V to 0.5V 4.5 to 0.5V 4.5 Vdc 0.5 Vdc
20 to 0mA (10 to 0V) 10 to 0V 10 Vdc 0 Vdc
Parameter 62
Stepper sign.vol
(min.) 000%
BPQ, XPQ
Voltage controller: minimum value 0 to 100%
This parameter permits the operator to clamp or limit the lower limit of the analog
output signal.
Example:
A 1 to 4V analog output is needed for the voltage controller to operate
properly. A jumper is installed on terminals 8/9 as described above and the analog
output signal of 0 to 5V is selected. The number to be configured as the minimum
output signal in this parameter is determined by dividing the desired lower limit by
the range of the signal (1V/5V = 0.20 or 20%). 20% is the value to be configured in
this parameter.
Parameter 63
Stepper sign.vol
(max.) 000%
BPQ, XPQ
Voltage controller: maximum value 0 to 100%
This parameter permits the operator to clamp or limit the upper limit of the analog
output signal.
Example:
A 1 to 4V analog output is needed for the voltage controller to operate
properly. A jumper is installed on terminals 8/9 as described above and the analog
output signal of 0 to 5V is selected. The number to be configured as the maximum
output signal in this parameter is determined by dividing the desired upper limit by
the range of the signal (4V/5V = 0.80 or 80%). 80% is the value to be configured in
this parameter.

Table of Contents

Other manuals for Woodward GCP-30 Series

Related product manuals