207
Type
Terminal
Name
Function
output current 200mA. Cannot use for other ways, only for
X terminal power supply.
10V-GND
+10V power supply
Supply +10V power supply, max output current 20mA.
COM
Common terminal
of input X
When using the internal power supply to drive the X
terminal:
COM and 24V are short circuited to form NPN input;
COM and 0V are short circuited to form PNP input;
When using the external 24V power supply to drive the X
terminal:
COM is connected to external power supply 24V+,
disconnected from 24V of VH6 to form NPN input;
COM is connected to external power supply 0V,
disconnected from 0V of VH6 to form PNP input;
Digital input
terminal
X1
Input terminal 1
Optocoupler isolation input; compatible with bipolar
input;
Input impedance: R = 2
The input voltage range is 9 ~ 30V.
X2
Input terminal 2
X3
Input terminal 3
X4
Input terminal 4
In addition to the characteristics of X1-X3, it can also be
used as a high-speed pulse input channel;
The highest frequency is 50 kHz.
Digital output
terminal
Y1
Digital output
terminal 1
Open collector output;
Output voltage range: 0-24V;
Output current range: 0-50mA.
Relay output
terminal
TA1 TB1 TC1
Relay 1
Programmable defined as multi-function relay output
terminal;
TA-TC: normally close; TA-TB: normally open
Contactor capacity
AC250V/2A (COSΦ=1);
DC30V/1A.
Analog input
AI1-GND
Analog input AI1
Input voltage range: 0~10V (input impedance: 22KΩ);
Input current range: 0~20mA (input impedance: 500Ω);
Select voltage / current input by DIP switch.
AI2-GND
Analog input AI2
Analog output
AO1-GND
Analog output AO1
Voltage output range: 0~10V;
Current output range: 0~20mA;
Select voltage / current output by DIP switch.
Communication
485+, 485-
RS485 port
Standard RS485 port. Use twisted pair or shielded wire.
DIP switch
S1
AI1
OFF = 0-10V , ON = 0-20mA default is OFF
S2
AI2
OFF = 0-10V , ON = 0-20mA default is OFF
S3
AO1
OFF = 0-10V , ON = 0-20mA default is OFF

Table of Contents