208
Appendix A-3-2. VH6-B100 (Slot B IO card)
Overview
VH6-B100 is the expansion card of slot B, which can be used when the function or number of IO card of slot A
does not meet the field demand. It has 1 AI, 1 AO, 3 bipolar inputs, 1 YT and 1 YR.
VH6-B100 specifications
Type
Terminal
Name
Function
Power supply
24V-0V
+24V power supply
Supply 24V power supply for input terminal X. max
output current 200mA. Cannot use for other ways,
only for X terminal power supply.
10V-GND
+10V power supply
Supply +10V power supply, max output current 50mA.
COM
Common terminal of
input X
When using the internal power supply to drive the X
terminal:
COM and 24V are short circuited to form NPN input;
COM and 0V are short circuited to form PNP input;
When using the external 24V power supply to drive the
X terminal:
COM is connected to external power supply 24V+,
disconnected from 24V of VH6 to form NPN input;
COM is connected to external power supply 0V,
disconnected from 0V of VH6 to form PNP input;
Digital input
terminal
X5
Input terminal 5
Optocoupler isolation input; compatible with bipolar
input.
Input impedance: R = 2
The input voltage range is 9 ~ 30V.
X6
Input terminal 6
X7
Input terminal 7
Digital output
terminal
Y2
Digital output
terminal 1
Open collector output;
Output voltage range: 0-24V;
Output current range: 0-50mA;
Can be high speed pulse output 50KHz.
Relay output
terminal
TA2 TB2 TC2
Relay 2
Programmable defined as multi-function relay output
terminal;
TA-TB: normally open; TA-TC: normally close
Contactor capacity
AC250V/2A (COSΦ=1);
AC250V/1A (COSΦ=0.4);
DC30V/1A.
Analog input
AI3-GND
Analog input AI3
Input voltage range: -10~10V;
Support PT100;
Select the voltage/PT100 through the DIP switch.
Analog output
AO2-GND
Analog output AO2
Voltage output range: 0~10V;
Current output range: 0~20mA;
Select voltage / current output by DIP switch.
DIP switch
S1
AI3
OFF = -10-10V, ON =PT100 default is OFF
S2
AO2
OFF = 0-10V, ON = 0-20mA default is OFF

Table of Contents