222
(2) Non function code
Definition
Modbus address
Function
Note
Communication
setting
1000H
Communication frequency
Write
Control command
1100H
1: Forward running
2: Reverse operation
3: Forward jog
4: Reverse jog
5: Deceleration stop
6: Free stop
7: Fault reset
Write
Digital output
terminal control
1101H
bit0: Y1 output control
bit1: Y2 output control
bit2: Reserved
bit3: RELAY1 output control
bit4: RELAY2 output control
Write
Y2 high speed pulse
control
1102H
0~7FFF represents 0%~100%
Write
Analog output AO1
1103H
0~7FFF represents 0%~100%
Write
Analog output AO2
1104H
0~7FFF represents 0%~100%
Write
Torque setting
(3730 and above
versions)
1105H
0~1000 represents 0.0%~100.0%
Write
Operation status
1200H
1: Forward run
2: Reverse run
3: Stop
Read
VFD fault
1210H
0000H: None
0001H: Acceleration over current
0002H: Deceleration over current
0003H: Constant speed over current
0004H: Acceleration overvoltage
0005H: Deceleration overvoltage
0006H: Constant speed over voltage
0007H: Buffer resistance overload fault
0008H: Under voltage fault
0009H: Inverter overload
000AH: Motor overload
000BH: Input phase missing
000CH: Output phase missing
000DH: Radiator overheating
000EH: Contactor fault
000FH: Current detection fault
0010H: Motor tuning fault
0011H: Code disk failure
0012H: Motor short circuit to ground
Read