67
Group P7: Fault parameters
Parameter
Name
Setting range
Default
value
Modify
Modbus
address
0: Free stop
1: Stop as stop mode
Hundreds bit: PID feedback lost in
operation (Err50)
0: Free stop
1: Stop as stop mode
Thousands bit: speed deviation too
large (Err52)
0: Free stop
1: Stop as stop mode
Ten thousand bit: motor over speed
(Err53)
0: Free stop
1: Stop as stop mode
P7-48
Protection action selection 4 when
fault
Ones bit: motor overheat (Err54)
0: Free stop
1: Stop as stop mode
00
0730H
P7-52
Brake starting voltage
200.0V ~ 2000.0V
690V
0734H
P7-53
Utilization rate of brake resistor
0 ~ 100%
100%
0735H
P7-55
Over voltage stall gain
0 ~ 100
30
0737H
P7-56
Over voltage stall protection voltage
650V ~ 800V
760.0V
0738H
P7-61
Load drop detection level
0.0%~100.0%
10.0%
073DH
P7-62
Load drop detection time
0.0~60.0s
1.0s
073EH
P7-63
Over speed detection value
0.0% ~ 50.0% (unit is max
frequency P0-12)
20.0%
073FH
P7-64
Over speed detection time
0.0s~60.0s
1.0s
0740H
P7-65
Detection value of excessive speed
deviation
0.0% ~ 50.0%(unit is max
frequency P0-13)
20.0%
0741H
P7-66
Excessive speed deviation detection
time
0.0s ~ 60.0s
5.0s
0742H
P7-67
Selection of instantaneous stop
non-stop function
0: Transient power failure invalid
1:Deceleration in case of
instantaneous power failure
2:Deceleration stop in case of
instantaneous power failure
0
×
0743H
P7-68
Pause judgement voltage of transient
stop action
80.0%~100.0%
85.0%
×
0744H
P7-69
Judgment time of instantaneous stop
non-stop voltage rising
0.0s~30.0s
0.5s
×
0745H
P7-70
Judgement voltage of instantaneous
stop non-stop action
60.0%~100.0% (bus voltage)
80.0%
0746H
P7-71
Proportional gain of instantaneous stop
non-stop
0 ~ 100
40
0747H