No. Name Description Range Def.
Mode
Addr.
Hex
Pg.
V/f
H3-13
Analog Input
Filter Time
Constant
Sets the primary delay filter time constant for terminal
A1 or potentiometer (optional). Used for noise
filtering.
0.00 to
2.00
0.03 s O 41B
<22> Parameter can be changed during run.
No. Name Description Range Def.
Mode
Addr.
Hex
Pg.
V/f
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
H4-01
Multi-Function
Analog Output
Terminal AM
Selects the data to be output through multi-function
analog output terminal AM.
Set the desired monitor parameter to the digits
available in Uo-oo. For example, enter “103” for
U1-03.
When using this terminal in through mode or when
not using it at all, set “000” or “031”.
000 to
999
102 O 41D 104
H4-02
<22>
Multi-Function
Analog Output
Terminal AM
Gain
Sets terminal AM output level when selected monitor
is at 100%.
Maximum output voltage is 10 V.
-999.9 to
999.9
100.0
%
S 41E 104
H4-03
<22>
Multi-Function
Analog Output
Terminal AM
Bias
Sets terminal AM output level when selected monitor
is at 0%.
-999.9 to
999.9
0.0% O 41F 104
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
H5-01
<39>
Drive Slave
Address
Selects drive slave number (address) for MEMOBUS/
Modbus
terminals
R+,
R-,
S+,
S-.
Cycle
power for the
setting to take effect.
0 to FF 1F O 425
H5-02
Comm. Speed
Selection
Selects the baud rate for MEMOBUS/Modbus
terminals R+, R-, S+ and S-. Cycle power for the
setting to take effect.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19200 bps
5 : 38400 bps
0 to 5 3 O 426
H5-03
Comm. Parity
Selection
Selects the communication parity for MEMOBUS/
Modbus
terminals
R+,
R-,
S+
and
S-.
Cycle power for
the setting to take effect.
0: No parity
1: Even parity
2: Odd parity
0 to 2 0 O 427
H5-04
Stopping
Method After
Comm. Error
Selects the stopping method when a communication
time-out fault (CE) is detected.
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
0 to 3 3 O 428
B.2 Parameter Table
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
209
B
Parameter List
2/6/2008-14:44

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIMR-JA Series and is the answer not in the manual?

YASKAWA CIMR-JA Series Specifications

General IconGeneral
BrandYASKAWA
ModelCIMR-JA Series
CategoryController
LanguageEnglish

Related product manuals