4.8 Automatic Parameter Settings Optimized for Specific Applications (Application Presets)
142 YASKAWA SIEPC71061753C GA500 Technical Manual
4.8 Automatic Parameter Settings Optimized for Specific
Applications (Application Presets)
Show the frequency reference screen.
Note:
Press and hold to return to the frequency reference screen from any screen.
Use this procedure to set an application preset.
The drive has application presets to set the necessary parameters for different applications to their best values. Use
to find parameters that were changed automatically by the application preset function in A1-06.
Note:
Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization] to
initialize parameters.
Figure 4.24 Automatic Parameter Settings
Press and hold to go back to the frequency reference screen.
Note:
• Make sure that you do Auto-Tuning after you set A1-06 for a hoist application.
• You cannot directly set parameter A1-06. To set an application preset, first set A1-03 = 2220 to initialize parameters, then set this
parameter. If initializing all parameters will cause a problem, do not change the settings.
• When the drive applies the A1-06 setting, it will also reset the parameters automatically registered to A2-17 to A2-32 [User Parameters
17 to 32] when A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms].