11.13 o: Keypad-Related Settings
438 YASKAWA SIEPC71061753C GA500 Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o2-09
(050D)
Reserved - - 766
o2-19
(061F)
Expert
Parameter Write during
Uv
Lets you change parameters during Uv [Undervoltage].
0 : Disable
1 : Enabled
0
( 0, 1 )
767
o2-23
(11F8)
RUN
External 24V Powerloss
Detection
Sets the function to give a warning if the backup external 24 V power supply turns off
when the main circuit power supply is in operation.
0 : Disabled
1 : Enabled
0
(0, 1)
767
o2-26
(1563)
Alarm Display at Ext.
24V Power
When you connect a backup external 24 V power supply, this parameter sets the
function to trigger an alarm when the main circuit power supply voltage decreases.
Note:
The drive will not run when it is operating from one 24-Vexternal power supply.
0 : Disabled
1 : Enabled
0
(0, 1)
767
o2-27
(1565)
bCE Detection Selection
Sets drive operation if the Bluetooth device is disconnected when you operate the drive
in Bluetooth Mode.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
3
(0 - 4)
767
◆ o3: Copy Keypad Function
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o3-01
(0515)
Copy Keypad Function
Selection
Sets the function that saves and copies drive parameters to a different drive with the
keypad.
0 : Copy Select
1 : Backup (drive → keypad)
2 : Restore (keypad → drive)
3 : Verify (check for mismatch)
4 : Erase (backup data of keypad)
0
(0 - 4)
768
o3-02
(0516)
Copy Allowed Selection
Sets the copy function when o3-01 = 1 [Copy Keypad Function Selection = Backup
(drive → keypad)].
0 : Disabled
1 : Enabled
0
(0, 1)
768
o3-04
(0B3E)
Select Backup/Restore
Location
Sets the storage location for drive parameters when you back up and restore parameters.
This parameter is only available when using an LCD keypad.
0 : Memory Location 1
1 : Memory Location 2
2 : Memory Location 3
3 : Memory Location 4
0
(0 - 3)
768
o3-05
(0BDA)
Select Items to Backup/
Restore
Sets which parameters are backed up, restored, and referenced. This parameter is only
available when using an LCD keypad.
0 : Standard Parameters
1 : Standard + DWEZ Parameters
0
(0, 1)
768