Parameter List
11
11.13 o: Keypad-Related Settings
YASKAWA SIEPC71061753C GA500 Technical Manual 439
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o3-06
(0BDE)
Auto Parameter Backup
Selection
Sets the function that automatically backs up parameters. This parameter is only
available when using an LCD keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
769
o3-07
(0BDF)
Auto Parameter Backup
Interval
Sets the interval at which the automatic parameter backup function saves parameters
from the drive to the keypad.
Note:
This parameter is only available when using an LCD keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
1
(0 - 3)
769
◆ o4: Maintenance Monitors
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o4-01
(050B)
Elapsed Operating Time
Setting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
769
o4-02
(050C)
Elapsed Operating Time
Selection
Sets the condition that counts the cumulative operation time.
0 : U4-01 Shows Total Power-up Time
1 : U4-01 Shows Total RUN Time
0
(0, 1)
769
o4-03
(050E)
Fan Operation Time
Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-
hour units.
0 h
(0 - 9999 h)
770
o4-05
(051D)
Capacitor Maintenance
Setting
Sets the U4-05 [CapacitorMaintenance] monitor value.
0%
(0 - 150%)
770
o4-07
(0523)
Softcharge Relay
Maintenance Set
Sets the U4-06 [PreChargeRelayMainte] monitor value.
0%
(0 - 150%)
770
o4-09
(0525)
IGBT Maintenance
Setting
Sets the U4-07 [IGBT Maintenance] monitor value.
0%
(0 - 150%)
770
o4-11
(0510)
Fault Trace/History Init
(U2/U3)
Resets the records of Monitors U2-xx [Fault Trace] and U3-xx [Fault History].
0 : Disabled
1 : Enabled
0
(0, 1)
770
o4-12
(0512)
kWh Monitor
Initialization
Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-11 [kWh, Upper 5
Digits].
0 : No Reset
1 : Reset
0
(0, 1)
771
o4-13
(0528)
RUN Command Counter
@ Initialize
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Number of Runs
(Low)], and U4-25 [Number of Runs (High)].
0 : No Reset
1 : Reset
0
(0, 1)
771
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when using an LCD
keypad.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
0
(0 - 2)
771
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available when using an LCD
keypad.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
0
(0 - 2)
771
o4-24
(310F)
RUN
bAT Detection Selection
Sets the operation when the drive detects bAT [Keypad Battery Low Voltage] and TiM
[Keypad Time Not Set]. This parameter is only available when you use an LCD keypad.
0 : Disable
1 : Enable (Alarm Detected)
2 : Enable (Fault Detected)
0
(0 - 2)
772