10.7 Drive Derating
342 YASKAWA SIEPC71061753C GA500 Technical Manual
Model
Rated Current (A)
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
2 kHz 5 kHz 8 kHz 10 kHz 12.5 kHz 15 kHz 2 kHz 5 kHz 8 kHz 10 kHz 12.5 kHz 15 kHz
4044 39.0 39.0 39.0 34.5 29.0 23.4 44.0 44.0 39.0 34.5 29.0 23.4
4060 45.0 45.0 45.0 39.9 33.4 27.0 60.0 54.5 46.3 40.8 33.9 27.0
Table 10.18 AOLV/PM Carrier Frequency and Rated Current Derating (Three-Phase 400 V)
Model
Rated Current (A)
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz
4001 1.2 1.2 1.1 0.9 0.7 0.5 1.2 1.2 1.1 0.9 0.7 0.5
4002 1.8 1.8 1.7 1.4 1.1 0.8 2.1 2.0 1.7 1.4 1.1 0.8
4004 3.4 3.4 3.2 2.6 2.0 1.5 4.1 3.8 3.2 2.6 2.0 1.5
4005 4.8 4.8 4.5 3.7 2.9 2.1 5.4 5.3 4.5 3.7 2.9 2.1
4007 5.5 5.5 5.2 4.2 3.3 2.4 7.1 6.2 5.2 4.3 3.3 2.4
4009 7.3 7.3 6.9 5.6 4.4 3.1 8.9 8.1 6.9 5.6 4.4 3.1
4012 9.2 9.2 8.7 7.1 5.5 3.9 11.9 10.3 8.7 7.1 5.5 3.9
4018 14.8 14.8 14.0 11.4 8.9 6.3 17.5 16.2 13.7 11.2 8.7 6.2
4023 18.0 18.0 17.0 13.9 10.8 7.7 23.4 20.3 17.1 14.0 10.8 7.7
4031 24.0 24.0 22.6 18.5 14.4 10.3 31.0 26.9 22.7 18.6 14.4 10.3
4038 31.0 31.0 29.2 23.9 18.6 13.3 38.0 34.5 29.2 23.9 18.6 13.3
4044 39.0 39.0 36.8 30.1 23.4 16.7 44.0 43.5 36.8 30.1 23.4 16.7
4060 45.0 45.0 42.4 34.7 27.0 19.3 60.0 51.8 43.5 35.3 27.0 18.8
Derating Depending on Ambient Temperature
When you install drives in these conditions, set L8-12 [Ambient Temperature Setting] and L8-35 [Installation
Method Selection].
Surrounding air temperatures are higher than the rated conditions
Install drives side-by-side in the enclosure panel
Derate the output current as specified in Figure 10.1.
A - L8-35 = 0 [IP20/UL Open Type] (0.5 m/s of
airflow around the drive is necessary)
B - L8-35 = 1 [Side-by-Side Mounting]
C - L8-35 = 2 [IP20/UL Type 1]
D - L8-35 = 3 [External Heatsink/Finless]
Figure 10.1 Derating Depending on Drive Installation Method
L8-12: Ambient Temperature Setting
No.
(Hex.)
Name Description
Default
(Range)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
40 °C
(-10 °C - +60 °C)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals