Parameter List
11
11.5 b: Application
YASKAWA SIEPC71061753C GA500 Technical Manual 371
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b8-25
(0B46)
Expert
PM E-Save Search Start
Level
Sets the start level for search operations.
10.0%
(0.0 - 100.0%)
544
b8-26
(0B47)
Expert
PM E-Save Power
Setpoint
Sets a value to increase torque accuracy.
0.0%
(-10.0 - +10.0%)
545
b8-28
(0B8B)
Expert
Over Excitation Action
Selection
Sets the function for excitation operation.
0 : Disabled
1 : Enabled
0
(0, 1)
545
b8-29
(0B8C)
Energy Saving Priority
Selection
Sets the priority of drive response between changes to the load or Energy-saving
control. Enable this to prioritize energy-saving control. Disable this to prioritize
tracking related to fast load changes, and prevent motor stall.
0 : Priority: Drive Response
1 : Priority: Energy Savings
0
(0, 1)
545
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals