3.6 Control Circuit Wiring
100 YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Note: Depending on parameter settings, either one or two boards can be inserted. In this table, it is assumed that one board is inserted.
Contact output
terminals
30
Major fault
Form-C contact relay
Single-phase, 220 Vac/15 A,
Single-phase, 110 Vac/15 A,
24 Vdc/15 A
Open: Major fault (32-31)
Closed: Major fault (32-30)
31
32
33
During run
Form-C contact relay
Single-phase, 220 Vac/15 A,
Single-phase, 110 Vac/15 A,
24 Vdc/15 A
Closed: During run (35-33)
Open: During run (35-34)
34
35
36
Drive ready
Form-C contact relay
Single-phase, 220 Vac/15 A,
Single-phase, 110 Vac/15 A,
24 Vdc/15 A
Closed: Drive ready (38-36)
Open: Drive ready (38-37)
37
38
39
Minor fault
N.O. contact relay
Single-phase, 220 Vac/15 A,
Single-phase, 110 Vac/15 A,
24 Vdc/15 A
Closed: Minor fault
40
41
Medium-voltage power
shutdown
Form-C contact relay
220Vac/55 A, 110 Vac/60 A
220 Vdc/1.5 A, 110 Vdc/5 A
Turning off
(Contact state during power off time)
Closed: Power turning OFF (41-42)
Open: Power turning OFF (41-43)
42
43
44
Reserved – –
45
91
Door interlock – –
92
Terminals for
inrush current
suppression
circuit
26
Inrush current suppression circuit
(Option)
N.O. contact relay output
Single-phase, 220 Vac/10 A,
24 Vdc/10 A
MC_ON signal
(Output in response to Drive Ready)
28
27 N.C. contact relay output
Single-phase, 220 Vac/10 A,
24 Vdc/10 A
28
L47
Contact input
Single-phase, 220 Vac/8 mA
MC_ANS signal
(Closed by answer from inrush current
suppression panel)
L48
Terminals for
the PG
<1>
L19
Line driver
PG interface PG-X3
(Option)
A pulse signal input
Inputs the A and B signals
Signal levels: Equivalent to RS-422
L20 A inverse signal input
L21 B pulse signal input
L22 B inverse signal input
L23 PG power supply Output voltage:
12 V ± 5% or 5.5 V ± 5%
Max. output current: 200 mA
L24 PG power supply common
L25 Ground Grounds shielded lines
L19
Complementary type
PG interface PG-B3
(Option)
A+ pulse signal input
Inputs the A and B channel
Signal levels: High level: 8 to 12 V
Low level: 2.0 V or less
L20 A- pulse signal input
L21 B+ pulse signal input
L22 B- pulse signal input
L23 PG power supply
Output voltage: 12 V ± 5%
Max. output current: 200 mA
L24 PG power supply common
L25 Ground Grounds shielded lines
Terminals for
the
MEMOBUS/
Modbus
communications
L71
MEMOBUS/Modbus
communications
(Option)
R+
RS-485
L72 R-
L73 S+
L74 S-
<1> When a PG interface options is installed, only one type, either a line driver PG interface or a complementary type PG interface may be
chosen for use.
Type Terminal Signal Name Signal Level Terminal Function