3.6 Control Circuit Wiring
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions 99
3.6 Control Circuit Wiring
u Control Circuit Terminals
WARNING! Sudden Movement Hazard. After an emergency stop circuit has been wired, check to make sure that it is operating
properly. Emergency stop circuits are needed to safely and quickly stop the operation of the drive. Operating a drive
with an emergency stop circuit whose operation has not been checked could result in serious injury or death.
WARNING! Confirm the drive I/O signals and external sequence before starting the test run. Failure to comply may result in or
serious injury or death.
n Analog Input and Output Terminals
Table 3.8 Analog Input and Output Terminals
n Contact Input and Output Terminals
Table 3.9 Contact Input and Output Terminals
Type Terminal Signal Name Signal Level Terminal Function
Analog input
terminals
L1
Speed (frequency) reference
4 to 20 mA DC,
0 to 60 Hz
Speed (frequency) reference input
signal
L2 Ground
L3 Shield ground
Analog output
terminals
L4
Output frequency
4 to 20 mA DC,
0 to 60 Hz
Output frequency reference output
signal
L5 Ground
L6 Shield ground
L7
Output current
4 to 20 mA DC,
0 to 100%
Output frequency reference output
signal
L8 Ground
L9 Shield ground
Type Terminal Signal Name Signal Level Terminal Function
Contact input
terminals
1
Medium-voltage primary panel
on
Contact input
Single-phase, 220 Vac/8 mA
ON: Turning on (closed at default)
2
3
Operation interlock
Contact input
Single-phase, 220 Vac/8 mA
ON: Established (closed at default)
4
5
Reserved
−−
6
7
External fault reset
Contact input
Single-phase, 220 Vac/8 mA
ON: Reset
8
9
Reserved
−−
10
13
Run command/Stop command
Contact input
Single-phase, 220 Vac/8 mA
ON: Run
14
15 OFF: Stop
44
Reserved
−−
45