4.6 Auto-Tuning
126 YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
u Auto-Tuning Operation Example
The following example demonstrates Rotational Auto-Tuning when using Closed Loop Vector (A1-02 = 3).
n
Selecting the Type of Auto-Tuning
n Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.
Operating Procedure LCD Display
1 The control power supply is powered up. The initial display will appear.
2
Press the or key until the Auto-Tuning display will appear.
3
Press to begin setting parameters.
4
Press to select the value for T1-01.
<1>
<1> T1-00 will appear on the display when one of the multi-function inputs has been set to switch between motor 1 and motor 2 (H1- =
16).
5
Save the setting by pressing .
6 The display automatically returns to the display shown in Step 3.
Operating Procedure LCD Display
1
Press to access the motor output power parameter T1-02.
2
Pressing displays the value set in E2-11 (Motor rated capacity) when the
control power is energized.
3
Press , , , and to enter the motor power
nameplate data in kW.
4
Press to save the setting.
5 The display automatically returns to the display in Step 1.
HELP
- MODE - PRG
Auto-Tuning
DATA
AUTO
FWD
- A.TUNE -
T1-01= 0
∗0∗
Standard Tuning
PRG
Tuning Mode Sel
ESC FWD D ATA
- A.TUNE -
T1-01= 0
∗0∗
Standard Tuning
PRG
Tuning Mode Sel
FWD
“0”
Entry Accepted
- A.TUNE -
T1-01= 0
∗0∗
Standard Tuning
PRG
Tuning Mode Sel
ESC FWD D ATA
- A.TUNE -
T1-02= 20000kW
(0 ~ 65000)
PRG
Mtr Rated Power
ESC FWD DATA
“20000kW”
- A.TUNE -
T1-02= 20000kW
(0 ~ 65000)
PRG
Mtr Rated Power
FWD
“20000kW”
F1
F2
- A.TUNE -
T1-02= 25000kW
(0 ~ 65000)
PRG
Mtr Rated Power
FWD
“20000kW”
Entry Accepted
- A.TUNE -
T1-02= 25000kW
(0 ~ 65000)
PRG
Mtr Rated Power
ESC FWD DATA
“20000kW”