124 YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
4.6 Auto-Tuning
4.6 Auto-Tuning
u Types of Auto-Tuning
Select the optimal Auto-Tuning based on the conditions such as your application, control mode of the drive, and
installation environment of the motor. When selecting the Auto-Tuning to run, refer to the flowcharts shown in Start-Up
Flowcharts on page 120.
Note: Only the Auto-Tuning parameters valid for the control mode set in A1-02 are shown.
n Auto-Tuning for Induction Motors
This feature automatically sets the following parameters for induction motors automatically:
• Motor parameters E1- and E2- (E3-, E4- for motor 2)
•F1- parameters for speed feedback detection (only when Closed Loop Vector Control is set)
Table 4.6 Types of Auto-Tuning for Induction Motors
Table 4. 7 lists the data that must be entered for Auto-Tuning. The necessary information is usually listed on the motor
nameplate or in the motor test report provided by the motor manufacturer. For details on the procedure for Auto-Tuning,
refer to Subchart A-1: Parallel Operation of Multiple Motors by V/f Control on page 121 or Subchart A-2: High
Performance Operation Using OLV or CLV on page 122 for details on Auto-Tuning processes and selections.
Table 4.7 Input Data for Auto-Tuning for Induction Motors
Type
Parameter
Setting
Application Condition and Benefit
Control Mode to Be
Applied
Rotational Auto-Tuning T1-01 = 0
• The motor can turn around during the Auto-Tuning:
This allows the most precise control of the motor.
• Running with constant output
Open Loop Vector Control
Closed Loop Vector Control
Stationary Auto-Tuning
for Line-to-Line
Resistance
T1-01 = 2
• Tunes the drive after the cable between the drive and
motor has been replaced with a cable over 50 m long.
Assumes Auto-Tuning has already been performed.
• Drive and motor capacities differ.
V/f Control
Open Loop Vector Control
Closed Loop Vector Control
Input Data
<1> Set when Closed Loop Vector control is selected.
Parameter Units
Auto-Tuning Type (T1-01)
Rotational Auto-Tuning (0)
Auto-Tuning for
Line-to-Line Resistance (2)
Motor Rated Capacity T1-02 kW Yes Yes
Motor Rated Voltage T1-03 V Yes No
Motor Rated Current T1-04 A Yes Yes
Motor Base Frequency T1-05 Hz Yes No
Number of Motor Pole T1-06 – Yes No
Motor Base Speed T1-07
r/min
Yes No
PG Number of Pulses Per
Revolution
T1-08 ppr <1> No