3.6 Control Circuit Wiring
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions 101
■ Control Power Supply Input Terminals
Table 3.10 Control Power Supply Input Terminals
◆ Control Circuit Terminal Layout and Specifications
The control circuit terminals are arranged on a terminal block as shown in Figure 3.19.
Figure 3.19
Figure 3.19 Terminal Configuration
■ Wire Gauges and Tightening Torque
Select appropriate wire type and gauges from Table 3.11.
Table 3.11 Wire Gauges and Torque Specifications
Type Terminal Terminal Function
Control power supply input terminal
RC
Single-phase 200/220 Vac
50/60 Hz
SC
Ground terminal ED Grounding of the control system
Terminal Type Terminal
Screw
Size
Tightening
Torque
(N•m)
Applicable Gauge
(mm
2
)
Recommended
Gauge
(mm
2
)
Wire Type
Analog input and
output terminals
L1 to L9 M3.5 0.8 to 1.0
0.5 to 2
<2>
1.25
Shielded twisted-pair wire
<1>
Contact input
and output
terminals
1 to 45 M3.5 0.8 to 1.0
0.5 to 2
<2>
1.25
Insulated vinyl sheathed cable (CVV) for
control circuit
Terminals for
inrush current
suppression
circuit
26 to 28
L47 to L48
M3.5 0.8 to 1.0
0.5 to 2
<2>
1.25
Insulated vinyl sheathed cable (CVV) for
control circuit
Control power
supply input
terminals
RC
SC
M5 2 to 2.5
8 to 14
<2>
8
600-V insulated vinyl sheathed cable
(VV)
Ground input
terminals
ED M5 2 to 2.5
8 to 14 <2>
8
600-V insulated vinyl sheathed cable
(VV)
Terminals for the
PG
L19 to L25 M3.5 0.8 to 1.0
0.5 to 2
<2>
1.25
Shielded twisted-pair wire <1>
Terminals for
monitor of motor
windings
18 to 21
L26 to L37
M3.5 0.8 to 1.0
0.5 to 2
<2>
1.25
Insulated vinyl sheathed cable (CVV) for
control circuit
ED
Reserved
1 to 45
L1 to L9
L19 to L25
L26 to L37
L38 to L45
L47 to L48
L71 to L74
26 to 28
22 to 25
18 to 21
(Option)
$0.$0.
RC
(Option)
RC1
SC1
SC