5.3 Types of Faults, Alarms, and Errors
144 YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
u Fault, Alarm and Error Displays
n Faults (Drive Faults and Power Cell Faults)
Table 5. 6 gives an overview of possible fault codes. Conditions such as overvoltages can trip faults and alarms. It is
important to distinguish between faults and alarms to determine the proper corrective actions.
When the drive detects a fault, the ALM indicator LED lights continuously and the fault code appears on the digital
operator. An alarm is present if the ALM LED blinks and the fault code on the digital operator flashes. Refer to Minor
Faults and Alarms on page 145 for a list of alarm codes.
Table 5.6 Fault Displays (1)
Digital Operator
Display
Name Page
Digital Operator
Display
Name Page
24V Optional Power Supply Error 148 EF0 Option Card External Fault 152
bUS Option Communication Error 148 EF1 to EF16 External Fault (input terminal) 152
CE
MEMOBUS/Modbus
Communication Error
148
Err EEPROM Write Error 153
FAn Fan Fault 153
FbH Excessive PID Feedback 153
CF Control Fault 149 FbL PID Feedback Loss 154
CFA
nn COF
<1>
Current Offset Fault 149 GF Ground Fault 154
CFA
nn CUV
<1>
Undervoltage 149 IOV Input Overvoltage 154
CFA
nn FU
<1>
Fuse Blowout 149 IUV Power Supply Undervoltage 154
CFA
nn IGBT_FLT
<1>
IGBT Fault 149 LF Output Phase Loss 154
CFA
nn OC
<1>
Overcurrent 150
LIN
nn LINK FAULT
<1>
CCB-MB Communication Error
(Link Fault)
155
CFA
nn OH
<1>
IGBT Overheating 150 oFA00
Option Card Connection Error at
Option Port CN5-A
155
CFA
nn OH1
<1>
IGBT Overheating 1 150 oFA01, oFA02
Option Card Fault at Option Port
CN5-A
155
CFA
nn OV
<1>
Overvoltage 1 150 oFA03 to oFA06
Option Card Error Occurred at
Option Port CN5-A
155
CFA
nn OV2
<1>
Overvoltage 2 150 oFA10, oFA11
Option Card Error Occurred at
Option Port CN5-A
155
CFA
nn VCF_OV
<1>
Main Circuit Capacitor Neutral Point
Potential Error
151 oFA12 to oFA17
Option Card Fault at Option Port
CN5-A
155
CPF00, CPF01 <2> Control Circuit Error 151 oFA30 to oFA43
Option Card Error Occurred at
Option Port CN5-A
155
CPF02 A/D Conversion Error 151 oFb00
Option Card Connection Error at
Option Port CN5-B
155
CPF06 EEPROM Memory Data Error 151 oFb01, oFb02
Option Card Fault at Option Port
CN5-B
155
CPF20, CPF21
<2> Control Circuit Error 151 oFb03 to oFb11
Option Card Error Occurred at
Option Port CN5-B
156
CPF22 Hybrid IC Error 151 oFb12 to oFb17
Option Card Fault at Option Port
CN5-B
156
CPF23 Control Board Connection Error 151 oFC00
Option Card Connection Error at
Option Port CN5-C
156
CPF26 to CPF29
Control Circuit Error 151
oFC01, oFC02
Option Card Fault at Option Port
CN5-C
156
CPF31 to CPF34
CPF40 to CPF43
oFC03 to oFC11
Option Card Error Occurred at
Option Port CN5-C
156
dEv
Speed Deviation (for Control Mode
with PG)
152
oFC12 to oFC17
Option Card Fault at Option Port
CN5-C
156
dO
Door Open 152