5.4 Fault Detection
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions 151
Troubleshooting
5
Digital Operator Display Fault Name
CFA
nn VCF_OV
Main Circuit Capacitor Neutral Point Potential Error
The P side or N side voltage in the DC bus has become unbalanced.
Cause Possible Solutions
The bus capacitor circuit has deteriorated or
there was a Power Cell fault.
Replace the electrolytic capacitor.
Check the balance resistance.
Check the cable.
Replace the cell control board.
Digital Operator Display Fault Name
CPF00, CPF01
<1>
Control Circuit Error
CPF20, CPF21
<1>
Cause Possible Solutions
There is a self-diagnostic error in control circuit.
Cycle control power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
Connector on the digital operator is damaged. Replace the digital operator.
Digital Operator Display Fault Name
CPF02
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
Cause Possible Solutions
Control circuit is damaged.
Cycle control power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
Digital Operator Display Fault Name
CPF06
EEPROM Memory Data Error
There is an error in the data saved to EEPROM.
Cause Possible Solutions
There is an error in EEPROM control circuit.
Cycle control power to the drive.
If the problem continues, replace the control board. For instructions on replacing it, contact
Yaskawa or your nearest sales representative.
The power supply was switched off while
parameters were being saved to the drive and the
communication option card was in use.
Reinitialize the drive (A1-03 = 2220).
Digital Operator Display Fault Name
CPF22 Hybrid IC Error
Cause Possible Solutions
Hybrid IC failure on the power board
Cycle control power to the drive.
If the problem continues, replace the control board. For instructions on replacing it, contact
Yaskawa or your nearest sales representative.
Digital Operator Display Fault Name
CPF23
Control Board Connection Error
Connection error between the control board and the Power Cell
Cause Possible Solutions
Hardware is damaged.
Turn off the power for the main circuit and controls and check the connection between the
control board and the Power Cell.
If the problem continues, replace either the control board or the entire drive. For instructions
on replacing the control board, contact Yaskawa or your nearest sales representative.
Digital Operator Display Fault Name
CPF26 to CPF29
Control Circuit ErrorCPF31 to CPF34
CPF40 to CPF43
Cause Possible Solutions
Hardware is damaged.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.