4.9 Checking and Saving Parameter Default Values
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions 135
Start-Up Programming
& Operation
4
n Operation Procedure of Copy Function (Digital Operator)
The digital operator will allow the following operations depending on the setting for parameter o3-01, Copy Function
Selection:
INV → OP READ (o3-01 = 1)
Stores the parameter settings of one drive in the digital operator.
Note: The number of the read operations of the digital operator is limited. The maximum number of read operations available is about
100,000 times.
OP → INV WRITE (o3-01 = 2)
Copies parameters from the digital operator to the drive.
OP → INV VERIFY (o3-01 = 3)
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
The read procedure is described below:
Note: Set o3-02, Copy Allowed Selection, to 1 (Allowed) when performing read functions. Setting o3-02 to 0 disables the Copy
function and protects the parameters saved in the digital operator.
Operating Procedure LCD Display
1 Turn on the power supply.
Initial setting screen
2
Press or to display the parameter setting mode screen, and then press
.
3
Select o3-01 (Copy Function Selection) by , or , and press
.
4
Press or to select an operation. Select “01” (INV → OP Read) in this
example.
5
Press to starts the operation.
6
After the operation finishes, the screen automatically returns to the copy function
selection screen.
7
Press until the screen returns to the initial screen.
Initial setting screen
HELP
- MODE - PRG
DATA
Programming
FWD
←→
-PRMSET-
Copy Function Sel
o3-01= 0 *0*
COPY SELECT
PRG
FWD
←→
-PRMSET-
Copy Function Sel
o3-01= 1 *0*
INV→OP READ
PRG
FWD
0
INV→OP READING
READ
READ COMPLETE
End