5.6 Operator Programming Error
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions 171
Troubleshooting
5
Settings for N.C. and N.O. input for the following
functions were selected simultaneously:
External Search Command 1 and External Search
Command 2 (61 vs. 62)
Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
Motor Switch Command and Accel/Decel Time 2
(16 vs. 1A)
FWD Run Command (or REV) and FWD/REV Run
Command (2-wire) (40, 41 vs. 42, 43)
Motor Switch Command and Up 2/Down 2 Command
(16 vs. 75, 76)
Check if contradictory settings have simultaneously been assigned to the contact
input terminals.
Correct the contact input settings.
One of the following settings was entered while H1- =
2 (External Reference 1/2):
b1-15 or b1-16 set to 3 but no option card is connected
b1-15 = 1 (Analog Input) and H3-02 (Analog Input
Function Selection) is not set to 0 (Analog Frequency
Reference).
H2- = 38 (Drive Enabled) but H1- is not set to 6A
(Drive Enable) and 70 (Drive Enable 2).
A signed value (H3-01) is set for the analog input while
allocating the UP2/DOWN2 commands (75 and 76).
Cancel either setting.
Digital Operator Display Error Name
oPE05
Run Command/Frequency Reference Source Selection Error
The setting for executing a Run command or frequency reference from communication
option card input is not correct.
Cause Possible Solutions
Frequency reference is assigned to an option card
(b1-01 = 3) and an input option card is not connected to
the drive.
Reconnect the input option card to the drive.
The Run command is assigned to an option card
(b1-02 = 3) and an input option card is not connected to
the drive.
Although the digital card input is set for BCD special for a
5-digit input (F3-01 = 6), the data length is set for 8-bit or
12-bit (F3-03 = 0, 1).
Set the input data for 16 bit (F3-03 = 2)
The following values have been set while an AI-A3 option
card is installed:
The source of frequency reference setting is assigned to
an option card (b1-01 = 3).
The action for the analog card is set for separate
terminal input (F2-01 = 0).
Make sure parameters are set properly.
The content below is set at the same time but AI-A3
option is not connected:
b1-16 (Run Command Selection 2) = 3 (Option card)
•H1- = 2 (External reference 1/2 selection)
Make sure parameters are set properly.
Digital Operator Display Error Name
oPE06
Control Method Selection Error
Correct the setting for the control method.
Cause Possible Solutions
A control mode has been selected that requires a PG
option card to be installed
(A1-02 = 3), but no PG option card is installed.
Connect a PG option card.
Correct the value set to A1-02.