C.9  MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions  243
MEMOBUS/Modbus 
Communications
C
00C1H
Fault Contents 4
bit 0 External Fault at contact input terminal 3 (EF3)
bit 1 External Fault at contact input terminal 4 (EF4)
bit 2 External Fault at contact input terminal 5 (EF5)
bit 3 External Fault at contact input terminal 6 (EF6)
bit 4 External Fault at contact input terminal 7 (EF7)
bit 5 External Fault at contact input terminal 8 (EF8)
bit 6 Fan Fault (FAn)
bit 7 Overspeed (oS)
bit 8 Speed Deviation (dEv)
bit 9 PG Disconnect (PGo)
bit A Reserved
bit B Output Phase Loss (LF)
bit C Reserved
bit D External Digital Operator Connection Fault (oPr)
bit E EEPROM Write Error (Err)
bit F Reserved
00C2H
Fault Contents 5
bit 0 MEMOBUS/Modbus Communication Error (CE)
bit 1 Option Communication Error (bUS)
bit 2, 3 Reserved
bit 4 Control Fault (CF)
bit 5 Reserved
bit 6 Option Card External Fault (EF0)
bit 7 PID Feedback Loss (FbL)
bit 8 Undertorque Detection 1 (UL3)
bit 9 Undertorque Detection 2 (UL4)
bit A High Slip Braking oL (oL7)
bit B External Fault at contact input terminal 9 (EF9)
bit C External Fault at contact input terminal 10 (EF10)
bit D External Fault at contact input terminal 11 (EF11)
bit E External Fault at contact input terminal 12 (EF12)
bit F Hardware Fault (includes oF)
00C3H
Fault Contents 6
bit 0 Main Circuit Capacitor Neutral Point Potential Error (CFA VCF OV)
bit 1 to 6 Reserved
bit 7 PG Hardware Fault (PGoH)
bit 8, 9 Reserved
bit A Too Many Speed Search Restarts (SEr)
bit B to F Reserved
00C4H
Fault Contents 7
bit 0 PID Feedback Loss (FbH)
bit 1 External Fault at contact input terminal 1 (EF1)
bit 2 External Fault at contact input terminal 2 (EF2)
bit 3 Mechanical Weakening Detection 1 (oL5)
bit 4 Mechanical Weakening Detection 2 (UL5)
bit 5 Current Offset Fault (CFA COF)
bit 6 to F Reserved
Register No. Contents