Standards Compliance
5
5.2 European Standards
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 227
Figure 5.3 Wiring Example for DC Power Supply Input
WARNING! Electrical Shock Hazard. Do not ground the main circuit bus. Incorrect wiring can cause serious injury or death.
Note:
• Install a fuse for each drive when operating more than one drive. If one fuse blows, replace all fuses.
• Install the external filter (system) to comply with the EMC Directive.
Refer to Table 5.4 and Table 5.5 for the recommended fuses.
Table 5.4 Recommended Fuse (Three-Phase 200 V Class)
Drive Model
Fuse
Manufacturer: Bussmann
Model Quantity
2004 FWH-45B 2
2006 FWH-45B 2
2008 FWH-45B 2
2010 FWH-45B 2
2012 FWH-50B 2
2018 FWH-80B 2
2021 FWH-80B 2
2030 FWH-125B 2
2042 FWH-150B 2
2056 FWH-200B 2
2070 FWH-250A 2
2082
FWH-250A
FWH-300A
*1
2
2110
FWH-250A
FWH-275A
*1
2
2138
FWH-300A
FWH-350A
*1
2
2169
FWH-350A
FWH-450A
*1
2
2211
FWH-450A
FWH-600A
*1
2
2257
FWH-600A
FWH-700A
*1
2
2313
FWH-800A
FWH-1000A
*1
2
2360 FWH-1000A 2
2415 FWH-1000A 2
*1 Yaskawa recommends a fuse with a large rated current for applications with repeated loads.