5.2 European Standards
232 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
A - Grounding surface (Remove any
paint or sealant.)
B - Enclosure panel
C - Metal plate
D - Drive
E - Ground the shield.
F - Motor
G - Motor cable (Braided shield cable:
max. 10 m (32.8 ft))
H - Cable clamp
I - Grounding wire
J - EMC noise filter
Figure 5.6 EMC Noise Filter and Drive Installation Procedure
5. Connect the DC link choke to decrease harmonic distortion. Refer to DC Link Chokes on page 234 to select a
DC link choke.
Note:
• To maintain compliance with IEC/EN 61000-3-2 on drive models 2004, 2006, 4002, and 4004, install a DC link choke.
• The main circuit terminal block for the drive, and the terminal blocks for the DC link choke come in different shapes. The drive
has a European style terminal block, and the DC link choke has a round terminal block. Correctly prepare the ends of the wiring.