Standards Compliance
5
5.3 UL Standards
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 249
Model
Recommended Gauge (AWG, kcmil)
Crimp Terminal Part
Number
*1
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
-, +1 +3
4250
- - - - 2
P2-38R-X
S2-38R-X
- - - 1/0 × 2P - S1/0-38R-X
2/0 × 2P 2/0 × 2P -
- -
S2/0-38R-X
- - 3/0 × 2P S3/0-38R-5
4302
- - - - 2
P2-38R-X
S2-38R-X
- - - 1/0 × 2P - S1/0-38R-X
3/0 × 2P 3/0 × 2P - - - S3/0-38R-5
- - 4/0 × 2P - - S4/0-38R-5
4371
- - - - 1 S2-12R-X
- - - 3/0 × 2P - S3/0-12R-5
250 × 2P 250 × 2P - - - S250-12R-5
- - 350 × 2P - -
LCA350-12-X
LCAX350-12-6
4414
- - - - 1 S2-12R-X
- - - 4/0 × 2P - S4/0-12R-5
300 × 2P 300 × 2P - - -
LCA300-12-X
LCAX300-12-6
- - 400 × 2P - - LCA400-12-6
4477
- - - - 1/0 S1/0-12R-X
- - - 3/0 × 4P - S3/0-12R-5
- 4/0 × 4P 4/0 × 4P - - S4/0-12R-5
250 × 4P - - - - S250-12R-5
4568
- - -
- 2/0 S2/0-12R-X
3/0 × 4P - S3/0-12R-5
- 4/0 × 4P - - - S4/0-12R-5
250 × 4P
-
-
- -
S250-12R-5
- 300 × 4P
LCA300-12-X
LCAX300-12-6
4605
- - - - 2/0 S2/0-12R-X
- - - 4/0 × 4P - S4/0-12R-5
300 × 4P 300 × 4P - - -
LCA300-12-X
LCAX300-12-6
- - 400 × 4P - - LCA400-12-6
4720
- - - - 2/0 S2/0-12R-X
- - - 4/0 × 4P - S4/0-12R-5
300 × 4P 300 × 4P - - -
LCA300-12-X
LCAX300-12-6
- - 400 × 4P - - LCA400-12-6
*1 For use with PANDUIT Corp. heat-shrinkable tubing HSTT series or an equivalent UL recognized heat-shrinkable tubing rated 600 V
minimum.

Table of Contents

Other manuals for YASKAWA GA800 Series

Related product manuals