6.3 MEMOBUS/Modbus Communications
278 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Figure 6.9 Message Example When Reading the Contents of Holding Register
Loopback Test
The loopback test uses function code 08 (Hex.) and returns the command message as a response message. This test
checks communication between the master and slave. The test code and data can use desired values.
Figure 6.10 shows examples of messages given out when the loopback test is done with the drive of slave 1.
Figure 6.10 Message Example When Doing the Loopback Test
Writing to Multiple Holding Registers
You can write the data that you set to the number of holding registers set in function code 10 (hex). You must
configure the number of the holding registers and each 8 higher bits and 8 lower bits in order in the command
message for the write data. You can write to a maximum of 16 holding registers.
Figure 6.11 shows example messages when you use the PLC to set Forward run in the drive of slave 1 with a 60.00
Hz frequency reference.
When you rewrite the parameter value with the write command through the H5-11 [Comm ENTER Command Mode]
setting, you must use the Enter command to save and enable the contents of the changes. Refer to H5-11: Comm
ENTER Command Mode on page 889 and Enter Command on page 282 for more information.