3.3 Main Circuit Wiring
76 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Model Terminals
Recommended
Gauge
AWG, kcmil
Applicable Gauge
(IP20 Applicable
Gauge
*1
)
AWG, kcmil
Wire Stripping
Length
*2
mm
Terminal Screw
Tightening Torque
Nm (inlb)
Size Shape
2313
R/L1, S/L2, T/L3 4/0 × 2P
3 - 4/0 × 2P
(2/0 - 4/0 × 2P)
- M10 Hex self-locking nut
20
(177)
U/T1, V/T2, W/T3 3/0 × 2P
3 - 4/0 × 2P
(2/0 - 4/0 × 2P)
- M10 Hex self-locking nut
20
(177)
-, +1 250 × 2P
2 - 250 × 2P
(4/0 - 250 × 2P)
- M10 Hex self-locking nut
20
(177)
+3 1/0 × 2P
4 - 1/0 × 2P
(1/0 × 2P)
- M10 Hex self-locking nut
20
(177)
2
2 - 350
(-)
- M10 Hex bolt (slotted)
18 - 23
(159 - 204)
2360
R/L1, S/L2, T/L3 250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
- M12 Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3 250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
- M12 Hex self-locking nut
35
(310)
-, +1 350 × 2P
4/0 - 400 × 2P
(300 - 400 × 2P)
- M12 Hex self-locking nut
35
(310)
+3 3/0 × 2P
1/0 - 4/0 × 2P
(-)
- M12 Hex self-locking nut
35
(310)
1
1 - 350
(-)
- M12 Hex bolt (slotted)
32 - 40
(283 - 354)
2415
R/L1, S/L2, T/L3 250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
- M12 Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3 300 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
- M12 Hex self-locking nut
35
(310)
-, +1 350 × 2P
4/0 - 400 × 2P
(300 - 400 × 2P)
- M12 Hex self-locking nut
35
(310)
+3 3/0 × 2P
1/0 - 4/0 × 2P
(-)
- M12 Hex self-locking nut
35
(310)
1
1 - 350
(-)
- M12 Hex bolt (slotted)
32 - 40
(283 - 354)
*1 For IP20 protection, use wires that are in the range of applicable gauges.
*2 Remove insulation from the ends of wires to expose the length of wire shown.
*3 For wire gauges more than AWG 8, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 in∙lb to 40 in∙lb).
*4 Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*5 A junction terminal is necessary to connect a braking unit (CDBR-series) to terminals - and +3.