Parameter Details
12
12.6 E: Motor Parameters
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 775
E5-01: PM Motor Code Selection
No.
(Hex.)
Name Description
Default
(Range)
E5-01
(0329)
PM Motor Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to automatically set
some parameters to their correct settings.
FFFF
(0000 - FFFF)
Note:
If the drive hunts or shows an alarm after you use a motor code, use the keypad to enter the value shown on the nameplate to E5-xx.
When you use a PM motor other than a Yaskawa SMRA, SSR1, or SST4 series, set E5-01 = FFFF.
Figure 12.73 gives information about the motor code setting digits.
Figure 12.73 PM Motor Code
E5-02: PM Motor Rated Power
No.
(Hex.)
Name Description
Default
(Range)
E5-02
(032A)
PM Motor Rated Power
Sets the PM motor rated output in the units set in o1-58 [Motor Power Unit Selection].
Determined by o2-04, C6-01
(0.10 - 650.00 HP)
The drive will automatically set this parameter the next time you do Auto-Tuning.
PM Motor Parameter Settings
PM Stationary Auto-Tuning
PM Rotational Auto-Tuning
E5-03: PM Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E5-03
(032B)
PM Motor Rated Current
(FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
0.01 A: models 2004 to 2042, 4002 to 4023
0.1 A: models 2056 to 2415, 4031 to 4720
After you do these types of Auto-Tuning, the drive automatically will set E5-03 to the value input for PM Motor
Rated Current:
PM Motor Parameter Settings
PM Stationary Auto-Tuning
PM StaTun for Stator Resistance
PM Rotational Auto-Tuning
E5-04: PM Motor Pole Count
No.
(Hex.)
Name Description
Default
(Range)
E5-04
(032C)
PM Motor Pole Count
Sets the number of PM motor poles.
4
(2 - 120)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents