EasyManua.ls Logo

YASKAWA GA800 Series - Page 994

YASKAWA GA800 Series
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.11 o: Keypad-Related Settings
994 YASKAWA SIEPC71061737B GA800 Drive Technical Reference
No. Item
Number of
Characters
Description
14 Reserved 4 -
15 Encoding data 4 Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 1 through 10. A bit value of 1 shows that the data represents a
negative value. (Log monitor data 1 through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding data
= 0010010010 (Bin.) = 0092 (Hex.)
16 File number 6 Row number (Hex.) in the data log file
o5-01: Log Start/Stop Selection
No.
(Hex.)
Name Description
Default
(Range)
o5-01
(1551)
RUN
Log Start/Stop Selection
Sets the data log function. This parameter is only available when using an LCD keypad.
0
(0 - 1)
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
o5-02: Log Sampling Interval
No.
(Hex.)
Name Description
Default
(Range)
o5-02
(1552)
RUN
Log Sampling Interval
Sets the data log sampling cycle. This parameter is only available when using an LCD keypad.
100 ms
(100 - 60000 ms)
o5-03: Log Monitor Data 1
No.
(Hex.)
Name Description
Default
(Range)
o5-03
(1553)
RUN
Log Monitor Data 1
Sets the data log monitor. This parameter is only available when using an LCD keypad.
101
(000, 101 - 999)
Note:
Set the U monitor number you want to log.
For example, to display U1-01 [Frequency Reference], set o5-03 = 101. When it is not necessary to set a data log monitor, set this parameter
to 000.
o5-04: Log Monitor Data 2
No.
(Hex.)
Name Description
Default
(Range)
o5-04
(1554)
RUN
Log Monitor Data 2
Sets the data log monitor. This parameter is only available when using an LCD keypad.
102
(000, 101 - 999)
Note:
Set the U monitor number you will log.
For example, to show U1-02 [Output Frequency], set o5-04 = 102. When it is not necessary to set data log monitor, set this parameter to
000.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800 Series

Related product manuals