12.11 o: Keypad-Related Settings
YASKAWA SIEPC71061737B GA800 Drive Technical Reference 995
■ o5-05: Log Monitor Data 3
No.
(Hex.)
Name Description
Default
(Range)
o5-05
(1555)
RUN
Log Monitor Data 3
Sets the data log monitor. This parameter is only available when using an LCD keypad.
103
(000, 101 - 999)
Note:
Set the U monitor number you want to log.
For example, to show U1-03 [Output Current], set o5-05 = 103. When it is not necessary to set a data log monitor, set this parameter to 000.
■ o5-06: Log Monitor Data 4
No.
(Hex.)
Name Description
Default
(Range)
o5-06
(1556)
RUN
Log Monitor Data 4
Sets the data log monitor. This parameter is only available when using an LCD keypad.
107
(000, 101 - 999)
Note:
Set the U monitor number you want to log.
For example, to show U1-07 [DC Bus Voltage], set o5-06 = 107. When it is not necessary to set a data log monitor, set this parameter to 000.
■ o5-07: Log Monitor Data 5
No.
(Hex.)
Name Description
Default
(Range)
o5-07
(1557)
RUN
Log Monitor Data 5
Sets the data log monitor. This parameter is only available when using an LCD keypad.
108
(000, 101 - 999)
Note:
Set the U monitor number you want to log.
For example, to show U1-08 [Output Power], set o5-07 = 108. When it is not necessary to set a data log monitor, set this parameter to 000.
■ o5-08: Log Monitor Data 6
No.
(Hex.)
Name Description
Default
(Setting Range)
o5-08
(1558)
RUN
Log Monitor Data 6
Sets the data log monitor. This parameter is only available when using an LCD keypad.
105
(000, 101 - 999)
(Wrong type value. Set note.)
• When A1-02 = 0 or 5 [Control Method Selection = V/f, OLV/PM], the default setting is 0.
• Set the U monitor number you want to log.
For example, to display U1-01 [Frequency Reference], set o5-08 = 101. When it is not necessary to set a data log monitor, set this
parameter to 000.
■ o5-09: Log Monitor Data 7
No.
(Hex.)
Name Description
Default
(Range)
o5-09
(1559)
RUN
Log Monitor Data 7
Sets the data log monitor. This parameter is only available when using an LCD keypad.
110
(000, 101 - 999)
Note:
Set the U monitor number you will log.
For example, to show U1-01 [Frequency Reference], set o5-09 = 101. When it is not necessary to set data log monitor, set this parameter to
000.