7.8 H: Terminal Functions
196 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Setting Value Function Description
24 External Fault (NO-Always-
Coast)
When the terminal activates, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or running.
25 External Fault (NC-Always-
Coast)
When the terminal deactivates, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or running.
26 External Fault (NO-@Run-
Coast)
When the terminal activates during run, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is stopped.
27 External Fault (NC-@Run-
Coast)
When the terminal deactivates during run, the drive shuts off the output and the motor coasts to stop. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is stopped.
28 External Fault (NO-Always-
FStop)
When the terminal activates, the drive stops the motor in the deceleration time set to C1-09 [Fast Stop Time]. Fault relay output
terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or
running.
29 External Fault (NC-Always-
FStop)
When the terminal deactivates, the drive stops the motor in the deceleration time set to C1-09 [Fast Stop Time]. Fault relay output
terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or
running.
2A External Fault (NO-@Run-
FStop)
When the terminal activates during run, the drive stops the motor in the deceleration time set to C1-09 [Fast Stop Time]. Fault relay
output terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is
stopped.
2B External Fault (NC-@Run-
FStop)
When the terminal deactivates during run, the drive stops the motor in the deceleration time set to C1-09 [Fast Stop Time]. Fault
relay output terminal MA-MC will turn ON, and MB-MC will turn OFF. The drive does not detect external faults while the drive is
stopped.
2C External Fault (NO-Always-
Alarm)
When the terminal activates, the keypad shows EFx [External Fault (Terminal Sx)] and the output terminal set for Alarm [H2-01 to
H2-03 = 10] activates. The drive continues operation. The drive always detects external faults whether the drive is stopped or
running.
2D External Fault (NC-Always-
Alarm)
When the terminal deactivates, the keypad shows EFx [External Fault (Terminal Sx)] and the output terminal set for Alarm [H2-01
to H2-03 = 10] activates. The drive continues operation. The drive always detects external faults whether the drive is stopped or
running.
2E External Fault (NO-@Run-
Alarm)
When the terminal activates during run, the keypad shows EFx [External Fault (Terminal Sx)] and the output terminal set for Alarm
[H2-01 to H2-03 = 10] activates. The drive continues operation. The drive does not detect external faults while the drive is stopped.
2F External Fault (NC-@Run-
Alarm)
When the terminal deactivates during run, the keypad shows EFx [External Fault (Terminal Sx)] and the output terminal set for
Alarm [H2-01 to H2-03 = 10] activates. The drive continues operation. The drive does not detect external faults while the drive is
stopped.
30 PID Integrator Reset Sets the command to reset and hold the PID control integral to 0 when the terminal is ON.
31 PID Integrator Hold Sets the command to hold the integral value of the PID control while the terminal is activated.
34 PID Soft Starter Disable Sets the PID soft starter function.
ON : No
OFF : Yes
35 PID Input (Error) Invert Sets the command to turn the terminal ON and OFF to switch the PID input level (polarity).
3E PID Setpoint Selection 1 Sets the function to switch the PID setpoint to YA-02 [Setpoint 2] or YA-04 [Setpoint 4]. Set this function and H1-xx = 3F [PID
Setpoint Selection 2] at the same time.
Note:
If you use this function and one of H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04] at the same time, the drive will
detect an oPE03 [Multi-Function Input Setting Err].
ON : YA-02 or YA-04 is PID setpoint.
OFF : The frequency reference, YA-01 [Setpoint 1], or YA-03 [Setpoint 3] is PID setpoint.
3F PID Setpoint Selection 2 Sets the function to switch the PID setpoint to YA-03 [Setpoint 3] or YA-04 [Setpoint 4]. Set this function and H1-xx = 3E [PID
Setpoint Selection 1] at the same time.
Note:
If you use this function and one of H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04] at the same time, the drive will
detect an oPE03 [Multi-Function Input Setting Err].
ON : YA-03 or YA-04 is PID setpoint.
OFF : The frequency reference, YA-01 [Setpoint 1], or YA-02 [Setpoint 2] is PID setpoint.
40 Forward RUN (2-Wire) This function will not operate in a bypass system.
Sets the Forward Run command for 2-wire sequence 1.
ON : Forward Run
OFF : Run Stop
44 Add Offset Frequency 1 (d7-
01)
Sets the function to add the offset frequency set in d7-01 [Offset Frequency 1] to the frequency reference when the terminal
activates.
45 Add Offset Frequency 2 (d7-
02)
Sets the function to add the offset frequency set in d7-02 [Offset Frequency 2] to the frequency reference when the terminal
activates.
46 Add Offset Frequency 3 (d7-
03)
Sets the function to add the offset frequency set in d7-03 [Offset Frequency 3] to the frequency reference when the terminal
activates.
51 Sequence Timer Disable Sets the command to disable Sequence Timers.
ON : Sequence Timer is Disabled