Table 4.16 Derated Torque Characteristics, Settings 4 to 7
Setting = 4 50 Hz Setting = 5 50 Hz Setting = 6 60 Hz Setting = 7 60 Hz
0
8
200
1.3 25 50
35
Voltage (V)
Frequency (Hz)
0
9
200
1.3 25 50
50
Voltage (V)
Frequency (Hz)
0
8
200
1.5 30 60
35
Voltage (V)
Frequency (Hz)
0
9
200
1.5 30 60
50
Voltage (V)
Frequency (Hz)
Table 4.17 High Starting Torque, Settings 8 to B
Setting = 8 50 Hz Setting = 9 50 Hz Setting = A 60 Hz Setting = B 60 Hz
0
11
200
1.3 2.5 50
19
Voltage (V)
Frequency (Hz)
0
13
200
1.3 2.5 50
24
Voltage (V)
Frequency (Hz)
0
11
200
1.5 3 60
19
Voltage (V)
Frequency (Hz)
0
15
200
1.5 3 60
24
Voltage (V)
Frequency (Hz)
Table 4.18 Rated Output Operation, Settings C to F
Setting = C 90 Hz Setting = D 120 Hz Setting = E 180 Hz Setting = F 60 Hz
0
9
15
200
1.5 3 9060
Voltage (V)
Frequency (Hz)
0
9
15
200
1.5 3 12060
Voltage (V)
Frequency (Hz)
0
9
15
200
1.5 3 18060
Voltage (V)
Frequency (Hz)
0
10.2
17.3
230
1.5 3 60
Voltage (V)
Frequency (Hz)
Predefined V/f Patterns for Models 2A0030 to 2A0211, 4A0018 to 4A0103, and 5A0011 to 5A0077
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V class drives.
Table 4.19 Rated Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz
0
7
200
1.3 2.5 50
14
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3 60
Voltage (V)
Frequency (Hz)
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3 6050
0
7
14
200
1.5 3 7260
Voltage (V)
Frequency (Hz)
Table 4.20 Derated Torque Characteristics, Settings 4 to 7
Setting = 4 50 Hz Setting = 5 50 Hz Setting = 6 60 Hz Setting = 7 60 Hz
Voltage (V)
Frequency (Hz)
0
6
200
1.3 25 50
35
0
7
200
1.3 25 50
50
Voltage (V)
Frequency (Hz)
Voltage (V)
Frequency (Hz)
0
6
200
1.5 30 60
35
0
7
200
1.5 30 60
50
Voltage (V)
Frequency (Hz)
4.6 Basic Drive Setup Adjustments
104
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide