Default Values for Fan and Pump Applications
Table 4.35 Fan and Pump Application Defaults
A1-03 Setting
Parameter 8008 8009 8010 8011
A1-02 0: V/f Control 0: V/f Control 0: V/f Control 0: V/f Control
b1-04 1: Reverse Disabled 1: Reverse Disabled
b3-05 10.0 s 10.0 s
b5-01 1: PID Enabled 1: PID Enabled
b5-03 5.0 s
b5-08 2.00 s
b5-13 2%
b5-14 25.0 s
b5-18 1: Enabled (b5-19) 1: Enabled (b5-19)
b5-20 3: User Set 3: User Set
b5-46 1: PSI
b5-89 1: EZ Sleep/Wake Up 1: EZ Sleep/Wake Up
C1-01 90.0 s 60.0 s
C1-02 90.0 s 60.0 s
C2-01 5.00 s 5.00 s
C2-02 5.00 s 5.00 s
C2-03 5.00 s 5.00 s
C2-04 5.00 s 5.00 s
H3-10 B: PID Feedback B: PID Feedback
L2-01 2: CPU Active 2: CPU Active 2: CPU Active 2: CPU Active
L3-02 110% 110%
L3-06 100% 100%
L4-05 0: Stop
L5-04 180.0 s 180.0 s
L5-05 1: L5-04 Interval 1: L5-04 Interval 1: L5-04 Interval 1: L5-04 Interval
o1-06 1: Selectable 1: Selectable
o1-07 102: Output Frequency 102: Output Frequency
o1-08 501: Feedback 501: Feedback
4.11 Fan and Pump Application Presets