u
Default Values for Fan and Pump Applications
Table 4.35 Fan and Pump Application Defaults
A1-03 Setting
Parameter 8008 8009 8010 8011
A1-02 0: V/f Control 0: V/f Control 0: V/f Control 0: V/f Control
b1-04 – – 1: Reverse Disabled 1: Reverse Disabled
b3-05 – – 10.0 s 10.0 s
b5-01 – 1: PID Enabled – 1: PID Enabled
b5-03 – – – 5.0 s
b5-08 – – – 2.00 s
b5-13 – – – 2%
b5-14 – – – 25.0 s
b5-18 – 1: Enabled (b5-19) – 1: Enabled (b5-19)
b5-20 – 3: User Set – 3: User Set
b5-46 – – – 1: PSI
b5-89 – 1: EZ Sleep/Wake Up – 1: EZ Sleep/Wake Up
C1-01 – – 90.0 s 60.0 s
C1-02 – – 90.0 s 60.0 s
C2-01 – – 5.00 s 5.00 s
C2-02 – – 5.00 s 5.00 s
C2-03 – – 5.00 s 5.00 s
C2-04 – – 5.00 s 5.00 s
H3-10 – B: PID Feedback B: PID Feedback
L2-01 2: CPU Active 2: CPU Active 2: CPU Active 2: CPU Active
L3-02 – – 110% 110%
L3-06 – – 100% 100%
L4-05 – – 0: Stop –
L5-04 – – 180.0 s 180.0 s
L5-05 1: L5-04 Interval 1: L5-04 Interval 1: L5-04 Interval 1: L5-04 Interval
o1-06 – 1: Selectable – 1: Selectable
o1-07 – 102: Output Frequency – 102: Output Frequency
o1-08 – 501: Feedback – 501: Feedback
4.11 Fan and Pump Application Presets
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
127
4
Start-Up Programming &
Operation