Drive Model
Normal Duty
Rated Amps (A)
<1>
Heatsink Loss (W) Interior Unit Loss (W) Total Loss (W)
4A0414 414 3443 1295 4738
4A0515 515 4850 1668 6518
4A0675 675 4861 2037 6898
4A0930 930 8476 2952 11428
4A1200 1200 8572 3612 12184
<1> Value assumes the carrier frequency is 2 kHz (C6-02 = 1, 7, 8, 9, or A).
Table A.12 Watt Loss Three-Phase 600 V Class Three-Phase Models
Drive Model
Normal Duty
Rated Amps (A)
<1>
Heatsink Loss (W) Interior Unit Loss (W) Total Loss (W)
5A0003 2.7 21.5 23.3 44.8
5A0004 3.9 27.5 33.6 61.1
5A0006 6.1 28.1 43.7 71.8
5A0009 9.0 43.4 68.9 112.3
5A0011 11 56.1 88.0 144.0
5A0017 17 96.6 146.7 243.2
5A0022 22 99.4 178.3 277.7
5A0027 27 132.1 227.2 359.3
5A0032 32 141.6 279.9 421.5
5A0041 41 330.8 136.2 467.0
5A0052 52 427.8 166.2 594.0
5A0062 62 791.2 279.0 1070.2
5A0077 77 959.1 329.4 1288.6
5A0099 99 1253.2 411.7 1664.9
5A0125 125 1641 537 2178
5A0145 145 1860 603 2463
5A0192 192 2420 769 3189
5A0242 242 3100 1131 4231
<1> Value assumes the carrier frequency is 2 kHz (C6-02 = 1, 7, 8, 9, or A).
A.3 Drive Watt Loss Data
182
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

Table of Contents

Other manuals for YASKAWA P1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA P1000 and is the answer not in the manual?

YASKAWA P1000 Specifications

General IconGeneral
Operating Temperature-10°C to +50°C (14°F to 122°F)
Cooling MethodFan Cooled
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
Frequency Range0.1-400 Hz
Power Rating0.4 kW to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit, Ground Fault
Protection FeaturesElectronic Thermal Overload Protection
CommunicationModbus RTU
Communication InterfaceRS-485
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Enclosure RatingIP20