Parameters 137
40.47 Set 1 wake-up
deviation
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay (40.48
Set 1 wake-up delay), the drive wakes up.
See also parameter 40.31 Set 1 deviation inversion.
0.00
-200000.00...2000
00.00
Wake-up level (as deviation between process setpoint and
feedback).
1 = 1
40.48 Set 1 wake-up
delay
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter 40.47 Set 1 wake-up
deviation.
The delay timer starts when the deviation exceeds the wake-
up level (40.47 Set 1 wake-up deviation), and resets if the
deviation falls below the wake-up level.
0.50
0.00…60.00 s Wake-up delay. 1 = 1
40.49 Set 1 tracking mode Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter 40.50 Set
1 tracking ref selection is substituted for the PID controller
output. See also section Tracking (page 40).
1 = Tracking mode enabled
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Supervision 1 Bit 0 of 32.01 Supervision status (see page 114). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 114). 22
Supervision 3 Bit 2 of 32.01
Supervision status (see page 114). 23
Other [bit] Source selection (see Terms and abbreviations on page 64). -
40.50 Set 1 tracking ref
selection
Selects the value source for tracking mode. See parameter
40.49 Set 1 tracking mode.
Not selected
Not selected None. 0
AI1 scaled 12.12 AI1 scaled value (see page 85). 1
AI2 scaled 12.22 AI2 scaled value (see page 86). 2
FB A ref1 03.05 FB A reference 1 (see page 70). 3
FB A ref2 03.06 FB A reference 2 (see page 70). 4
Other Source selection (see Terms and abbreviations on page 64). -
40.58 Set 1 increase
prevention
Prevention of PID integration term increase for PID set 1. No
No Increase prevention not in use. 0
Limiting The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is valid
for the PID set 1.
1
Other [bit] Source selection (see Terms and abbreviations on page 64). -
No. Name/Value Description Def/FbEq16