138 Parameters
40.59 Set 1 decrease
prevention
Prevention of PID integration term decrease for PID set 1. No
No Decrease prevention not in use. 0
Limiting The PID integration term is not decreased if the minimum
value for the PID output is reached. This parameter is valid
for the PID set 1.
1
Other [bit] Source selection (see Terms and abbreviations on page 64). -
40.60 Set 1 PID activation
source
Selects the source of process PID set 1 activation. On
Off Set 1 PID activation source is Off. 0
On Set 1 PID activation source is On. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 3
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 4
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 5
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 6
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 7
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 8
DIO1 Digital input/output DIO1. 9
DIO2 Digital input/output DIO2. 10
Other [bit] Source selection (see Terms and abbreviations on page 64). -
40.61 Setpoint scaling
actual
Actual setpoint scaling. See parameter 40.14 Set 1 setpoint
scaling.
0.00
-200000.00…
200000.00 PID
customer units
Scaling. 1 = 1 PID
customer unit
40.62 PID internal
setpoint actual
Shows value of the internal setpoint.
This parameter is read-only.
-
-200000.00…
200000.00
Process PID internal setpoint. 1 = 1
40.79 Set 1 units Selects the unit for process PID setpoint, feedback and
deviation.
°C
User text User text 0
%% 1
bar bar 2
kPa kPa 3
Pa Pa 4
psi psi 5
CFM CFM 6
inH
2
OinH
2
O7
°C °C 8
°F °F 9
mbar mbar 10
m
3
/h m
3
/h 11
dm
3
/h dm
3
/h 12
No. Name/Value Description Def/FbEq16