EasyManua.ls Logo

ABB ACS150 series

ABB ACS150 series
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Actual signals and parameters
125
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
2 = 3-WIRE
3-wire macro for constant speed applications
3 = ALTERNATE
Alternate macro for start forward and start reverse applications
4 = MOTOR POT
Motor potentiometer macro for digital signal speed control applications
5 = HAND/AUTO
Hand/Auto macro to be used when two control devices are connected to the
drive:
- Device 1 communicates through the interface defined by external control
location EXT1.
- Device 2 communicates through the interface defined by external control
location EXT2.
EXT1 or EXT2 is active at a time. Switching between EXT1/2 through digital
input.
6 = PID CONTROL
PID control. For applications in which the drive controls a process value. For
example, pressure control by the drive running the pressure boost pump.
Measured pressure and the pressure reference are connected to the drive.
31 = LOAD FD SET
FlashDrop parameter values as defined by the FlashDrop file. Parameter
view is selected by parameter 1611 PARAMETER VIEW.
FlashDrop is an optional device for fast copying of parameters to unpowered
drives. FlashDrop allows easy customisation of the parameter list, for
example, selected parameters can be hidden. For more information, see
MFDT-01 FlashDrop users manual (3AFE68591074 [English]).
0 = USER S1 LOAD
User 1 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
-1 = USER S1 SAVE
Save User 1 macro. Stores the current parameter settings and the motor
model.
-2 = USER S2 LOAD
User 2 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
-3 = USER S2 SAVE
Save User 2 macro. Stores the current parameter settings and the motor
model.
-4 = USER S3 LOAD
User 3 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the application.
-5 = USER S3 SAVE
Save User 3 macro. Stores the current parameter settings and the motor
model.

Table of Contents

Related product manuals