Technical data
142
Losses, cooling data and noise
Losses and cooling data
Frame size R0 has natural convection cooling. Frame sizes R1…R2 are provided
with an internal fan. The air flow direction is from bottom to top.
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O not in use) and maximum load (all digital
inputs in the on state and the fan in use). The total heat dissipation is the sum of the
heat dissipation in the main and control circuits.
T
y
p
e
ACS150-
x =
E/U
Heat
dissip
a
tion
Air flow
Main circuit
Control circuit
Rated I
1N
and
I
2N
Min
Max
W
BTU/Hr
W
BTU/Hr
W
BTU/Hr
m
3
/h
ft
3
/min
1-phase U
N
= 200…240 V (200, 208, 220, 230, 240 V)
01x-02A4-2
25
85
6
.3
22
12.3
42
-
-
01x-04A7-2
46
157
9.6
33
16.0
55
24
14
01x-06A7-2
71
242
9.6
33
16.0
55
24
14
01x-07A5-2
73
249
10.6
36
17.1
58
21
12
01x-09A8-2
96
328
10.6
36
17.1
58
21
12
3-phase U
N
= 200…240 V (200, 208, 220, 230, 240 V)
03x-02A4-2
19
65
6
.3
22
12.3
42
-
-
03x-03A5-2
31
106
6.3
22
12.3
42
-
-
03x-04A7-2
38
130
9.6
33
16.0
55
24
14
03x-06A7-2
60
205
9.6
33
16.0
55
24
14
03x-07A5-2
62
212
9.6
33
16.0
55
21
12
03x-09A8-2
83
283
10.6
36
17.1
58
21
12
3-phase U
N
= 380…480 V (380, 400, 415, 440, 460, 480 V)
03x-01A2-4
11
38
6
.7
23
13.3
45
-
-
03x-01A9-4
16
55
6
.7
23
13.3
45
-
-
03x-02A4-4
21
72
10.0
34
17.6
60
13
8
03x-03A3-4
31
106
10.0
34
17.6
60
13
8
03x-04A1-4
40
137
10.0
34
17.6
60
13
8
03x-05A6-4
61
208
10.0
34
17.6
60
19
11
03x-07A3-4
74
253
14.3
49
21.5
73
24
14
03x-08A8-4
94
321
14.3
49
21.5
73
24
14
00353783.xls
J
Noise
Frame size
Noise level
dBA
R0
<35
R1
52...55
R2
<62
00353783.xls
J