324 Parameters
Speed ref safe Drive generates an A7EE Panel loss warning and sets the
speed to the speed defined by parameter 22.41 Speed ref
safe (or 28.41 Frequency ref safe when frequency reference
is being used).
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
3
49.06 Refresh settings Applies the settings of parameters 49.01…49.05.
Note: Refreshing may cause a communication break, so
reconnecting the drive may be required.
Done
Done Refresh done or not requested. 0
Configure Refresh parameters 49.01…49.05. The value reverts
automatically to Done.
1
49.19 Basic panel home
view 1
Selects the parameters that is shown in Home view 1 of the
Basic panel (ACS-BP-S) when the active external control
location is EXT1.
Home view 1 is toggled automatically between Home view 4
(parameter 49.01) according to the active external control
location EXT1 or EXT2, respectively
Auto
Auto 01.06 Output frequency (page 165) in scalar control mode,
otherwise 01.01 Motor speed used used (page 165).
0
Motor speed used 01.01 Motor speed used 1
Output frequency 01.06 Output frequency 3
Motor current 01.07 Motor current 4
Motor current% of
motor nominal
01.08 Motor current % of motor nom 5
Motor torque 01.10 Motor torque 6
DC voltage 01.11 DC voltage 7
Output power 01.14 Output power
8
Speed ref ramp in 23.01 Speed ref ramp input 10
Speed ref ramp out 23.02 Speed ref ramp output 11
Freq ref used 28.02 Frequency ref ramp output 14
Process PID out 40.01 Process PID output actual 16
Temp sensor 1
excitation
The output is used to feed an excitation current to the
temperature sensor 1, see parameter 35.11 Temperature 1
source. See also section Motor thermal protection (page 82).
20
Temp sensor 2
excitation
The output is used to feed an excitation current to the
temperature sensor 2, see parameter 35.21 Temperature 2
source. See also section Motor thermal protection (page 82).
21
Abs motor speed
used
01.61 Abs motor speed used 26
Abs motor speed% 01.62 Abs motor speed % 27
Abs output
frequency
01.63 Abs output frequency 28
Abs motor torque 01.64 Abs motor torque 30
Abs output power 01.65 Abs output power 31
Abs motor shaft
power
01.68 Abs motor shaft power 32
AO1 data storage 13.91 AO1 data storage.37
No. Name/Value Description Def/FbEq16