PROFIdrive parameters
127
970 R/W Unsigned16 Load parameter record
Value Description
0 No action
1 Restore factory settings
The parameter must do a zero-to-one transition and the
motor must be stopped.
971 R/W Unsigned16 Save parameter record
Value Description
0 No action
1 Save the drive parameters to non-volatile
memory
The parameter must do a zero-to-one transition and the
motor must be stopped.
972 R/W Unsigned16 Software reset
Value Description
0 No action
1 Re-boot PROFIBUS module
The parameter must do a zero-to-one transition and the
motor must be stopped.
975 R Array[n]
Unsigned16
DO identification. For subindexes 0…4, see parameter
964.
Subindex Meaning
5 Value 2 = Axis
6 Bit 0=1
-
> Application Class 1 supported
Bit 2=1
-
> Application Class 3 supported
980
981
R Array[n]
Unsigned16
Number list of defined parameters. If the subindex is 0,
the end of the list has been reached. If the subindex is the
number of the next list parameter, the list is continued
there.
* Read and/or Write
** Support depends on drive type
Param-
eter
R/W
*
Data type Description