Quick start-up guide
22
Mechanical and electrical installation
• Insert the FPBA-01 into its specified slot in the drive.
• Fasten the screw.
• Plug the fieldbus connector to the module.
Drive configuration
• Power up the drive.
• The detailed procedure of activating the drive for
communication with the module is dependent on the drive type.
Normally, a parameter must be adjusted to activate the
communication. Refer to the drive documentation for
information on the communication settings. With an ACS350
drive, set parameter 9802 COMM PROT SEL to EXT FBA; with
an ACSM1 drive, set parameter 5001 FBA ENABLE to
ENABLE; and with an ACS850 drive, set parameter 5001 Fba
enable to Enable.
• Parameter group 51 shows the status of the FPBA configuration
parameters.
• At minimum, set the required node address at parameter 5102
NODE ADDRESS and the communication profile at 5105
PROFILE. Finally, validate the settings with 5127 FBA PAR
REFRESH.
Cyclic data handling
With the FPBA-01, both data-consistent and non-consistent
communication can be used, data-consistent meaning that the
whole cyclic data frame is transmitted during a single program
cycle. Some PLCs handle this internally, but others must be
programmed to transmit data-consistent telegrams (for more
information, see the chapter Communication). For example,
Siemens Simatic S7 requires the use of special functions SFC15
and SFC14.