The table below gives the recommended drive parameter settings.
Drive parameter Setting
50.01 Fba enable Enable
50.04 Fba ref1 modesel Speed
10.01 Ext1 start func FBA
21.01 Speed ref1 sel FBA ref1
51.01 FBA type 1 = FPBA-xx PROFIBUS DP
adapter module*
51.02 NODE ADDRESS 3
51.03 BAUDRATE 12000*
51.04 TELEGRAM TYPE 1 (= PPO 1)*
51.05 PROFILE 0 (= PROFIdrive)
52.01 FBA data in1 4*
52.02 Fba data in2 5
53.01 FBA data out1 1*
53.02 FBA data out2 2
51.27 FBA par refresh Refresh
*Read-only or automatically detected/set