FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E 67
Submenu / parameter Value range Remark
Selection of operating mode for empty tube detection.
• Standard: Factory adjustment to water, appropriate for most
measuring media.
• New adjustment: Start new adjustment to the current
medium.
Note
During adjustment, the pipe must be empty and fill afterwards.
Not displayed, if DEP is switched off.
Standard New adjustment
Adj. DLR empty Manual Menu visible when ‘New adjustment‘ is selected in the ‘DLR Mode‘
parameter. Adjustment value for empty meter pipe.
The pipeline must be empty.
• Automatic: Start the empty tube adjustment. After the
adjustment is completed, the transmitter displays the
adjustment value in the bottom line.
• Manual: Fine adjustment of the automatically determined
adjustment value.
Not displayed, if DEP is switched off or DEP mode is standard.
Menu visible when ‘New adjustment‘ is selected in the ‘DLR Mode’
parameter. Adjustment value for full meter pipe.
The piping must be completely filled.
• Automatic: Start the adjustment. After the adjustment is
completed, the transmitter displays the adjustment value in
the bottom line.
• Manual: Fine adjustment of the automatically determined
adjustment value.
Not displayed, if DEP is switched off or DEP mode is standard.
500 Automatic