FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E 83
Submenu Note
Once the self-test function is initiated, the transmitter no longer
operates in online mode, i.e., the outputs no longer track the
flowrate.
Test the memory. Internal FRAM, ext. FRAM and calc. Flash can be
queried in order via ENTER function.
Numerical entry This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Test the pulse output. Enter a value directly in Hz.
0 Hz
Current output 0 - 20 mA, 4 - 20 mA 0 -
10 mA, 2 - 10 mA
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Test the current output. Check the value displayed at the
connection terminals using a digital voltmeter or the process
instrumentation. Enter a value directly in mA.
No selection available if the HART device address is anything
other than 0.
Off
A
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Test the contact input. If no signal is applied to the switch input,
the text ‘Off’ is displayed in this menu. Once a signal is applied,
the text ‘On’ is displayed (to check via simulator, use the Totalizer
Reset button).
Off
Switch output Off
A
Test the contact output. When you set the value to ‘On’, the
switch output selected is displayed for the configured contact
logic under the item Switch Contacts - Switch Output.
Test the display. Every point in the dot matrix is activated one
after another. Once all points are activated, a missing point is
easily detected.
Test Mode Off
A
Only for checking the transmitter using Simulator 55XC4000.