96 FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
8 Operation
Parameter descriptions
Submenu / parameter
Value range
Remark
WMx ----------
WMi ----------
ConWarn -----
-----
ConErr---------
Submenu
Syst. Adjust
Start System Zero
Manual
Autom, adjustment
Check zero, if necessary (when adapting an older flowmeter
sensor). Manual entry, e.g., when replacing the transmitter.
0.0 %
System zero point Numerical entry Automatic adjustment: Valve must be closed, liquid in sensor
must be at absolute standstill. Press ENTER to perform the
automatic adjustment. The limit for the zero point is ± 10%. If
the value is outside this limit, no calibration is performed.
0.0 %
FSM4000 12/2019
Read only
Display software version. 01.2010 specifies the date of the
release. C.11 = Version level, for standard and HART protocol.
3KXF00001S0001 D.14
FSM4000 PA3.0 Read only For PROFIBUS PA software.
D699G004U02 C.13
FSM4000 FF
Read only
For FOUNDATION Fieldbus communication software.
D699G004U03 C.14