ABB i-bus
®
KNX
Parameters
88 2CDC509086D0201 | ABA/S 1.2.1
Function
Use of Flip Flop e.g. as an alarm memory.
No output value is actively set for the output.
Contingent initial values set can trigger an output change when the inputs receive an incoming signal.
O S R
O
new
0 0 0
0
0 0 1
0
0 1 0
1
0 1 1
0
1 0 0
1
1 0 1
0
1 1 0
1
1 1 1
0
As long as input R = 1, the output is always 0.
Bus voltage failure, download and restart
The values are stored. The last output value is restored on restart.