Loading...
2
101510 Rev. AG Page 6–
7
Additionally, component high/low concentration, component
peak not found, and component RF limit exceeded alarms
are available but disabled. These alarms may be enabled by
the user, but are not included here for the purposes of
troubleshooting. See the PCCU32 help files for more
information.
Table 6–1 NGC8200 Alarms
Description
Enable
Type
Severity
Pressure Regulator 1
Yes GT Fault
Pressure Regulator 2
Yes GT Fault
Sample Pressure
Yes GT Fault
Oven Temperature Error
Yes GT System Fault
No Stream Valve Selected
Yes GT System Fault
Digital-Analog Bd Comm Error
Yes GT System Fault
Calculation Error
Yes GT Fault
Calibration Un-Normalized Total
Yes GT Fault
Stream Sequence Error
Yes GT Fault
Calibration CV Percent Error
Yes GT Fault
RF Pct Error
Yes GT Fault
Analog Bd Ambient Temp
Yes GT Warning
Analog Power Supply
Yes GT Warning
Low Carrier Gas Bottle (DI1)
Yes LT Warning
Low Cal Gas Bottle (DI2)
Yes LT Warning
GCM Chrom Process
Yes GT System Fault
Bad Bead
Yes GT Fault
No Pilot Valve Change Detected
Yes GT Fault
Sample Flow Detect
Yes GT Fault
CPU Loading
Yes GT Warning
System Memory Available
Yes LT Warning
Ram File Available
Yes LT Warning
Flash File Available
Yes LT Warning
Missing Peak-Cal Not Used Yes GT Warning
Stream Un-Normalized Total Yes GT Warning
6.3.1 Operators
GT = Greater Than
LT = Less Than
And = Including
Or = Instead of
GE = Greater Than or Equal To
LE = Less Than or Equal To
NAND = And Not
Nor = Not Or

Table of Contents