PCS100 UPS-I User Manual 23
Rated power
kVA @ rated voltage
Inverter Rated
Current
[A]
Inverter Modules
Quantity
Utility Disconnect
Rated Current
[A]
Terminal Position
(Utility & Load)
Losses
kW (typical)
Efficiency
% (typical)
Airflow
(m
3
/min)
Standby
Fault Capacity
(l
cw
)
kA /
Withstand Period
ms
Frame Size
Type Code
To complete the Type
Code:
Place 5 for 50Hz or 6 for
60Hz in place of the X
480 V Models
150
180
1
900
L
2.3
98.5
27
25 / 10
1xB
PCS100-12-480/x0-01-L
300
361
2
900
L
3.2
98.9
27
25 / 10
1xB
PCS100-12-480/x0-02-L
450
541
3
900
L
4.3
99.1
27
25 / 10
1xA 1xB
PCS100-12-480/x0-03-L
600
722
4
900
L
5.5
99.1
27
25 / 10
1xB 1xC
PCS100-12-480/x0-04-L
750
902
5
900
L
6.6
99.1
35
50 / 120
1xA 2xC
PCS100-12-480/x0-05-L
900
1083
6
2200
R
7.1
99.2
35
50 / 120
1xA 1xB 1xC
PCS100-12-480/x0-06-R
1200
1443
8
2200
R
9.1
99.2
35
50 / 120
2xA 2xC
PCS100-12-480/x0-08-R
1500
1804
10
2200
R
11.2
99.3
35
50 / 120
2xA 1xC 1xF
PCS100-12-480/x0-10-R
1800
2165
12
2200
R
13.6
99.2
35
50 / 120
2xA 1xC 1xF
PCS100-12-480/x0-12-R
2100
2526
14
4200
R
14.9
99.3
45
65 / 120
3xA 1xC 1xF
PCS100-12-480/x0-14-R
2400
2887
16
4200
R
16.6
99.3
45
65 / 120
3xA 1xC 1xF
PCS100-12-480/x0-16-R
Table 3-2: PCS100 UPS-I model range (without energy storage)
Rated power
kVA @ rated voltage
Inverter Rated
Current
[A]
Inverter Modules
Quantity
Utility Disconnect
Rated
Current
[A]
Terminal Position
(Utility & Load)
Losses
kW (typical)
Efficiency
% (typical)
Airflow
(m
3
/min)
Standby
Fault Capacity
(l
cw
) kA
/
Withstand Period
ms
Frame Size
Type Code
To complete the Type
Code:
Place 5 for 50Hz or 6 for
60Hz in place of the X
440V model
2
(Note: This model uses 2 x 440 V, 1.5 MVA transformer)
3000
180
20
4200
R
23.5
99.3
45
65/120
4xA 2xC 2xF
PCS100-12-440/x0-20-L
Note:
208 V operation is achieved by setting a 220 V PCS100 UPS-I to 208 V.
380 V operation is achieved by setting a 400 V PCS100 UPS-I to 380 V.
415 V or 440 V operation is achieved by setting a 480 V PCS100 UPS-I to 415 V or 440 respectively.
This configuration is done at the factory and must be specified when ordering.
Note:
The Frame Size shown in Table 3-2 defines the standard PCS100 UPS-I in linear side-by side layout only. It does not
include the optional Fail-Safe Bypass enclosure or dummy enclosure options. If needed, for Fail-Safe Bypass
enclosure please add additional 1xC enclosure for a PCS100 UPS-I with load current greater than 900 A.
2
Only available for Ultracapacitor Energy Storage. Please contact the factory.