26 PCS100 UPS-I User Manual
4.2 Load – Output
208-220V 150 kVA to 1500kVA
400 V / 480 V 150 kVA to 2400kVA
Displacement Power Factor
of Connected Load
0.5 lagging to 0.9 leading
Crest Factor for Rated kVA
Maximum allowed motor
load
25% of rated kVA
Contact ABB for applications with greater than 25%
Overload Capability –
Inverter
<10% of rated kVA
See 9.7 for more detail. Contact ABB where load
imbalance is greater than 10% of rated kVA
<5% of rated current
See 9.7 for more detail. Contact ABB where neutral
current is greater than 5% of rated current
> 95% at end of discharge
Note: Model and load dependent. Displacement power
factor below 0.75 will incur greater voltage reduction.
50 or 60 Hz
Inverter frequency equals the supply frequency.
< 2.5% THDv for linear loads
Voltage unbalance
(negative / positive
sequence)
<3% for 100% unbalanced loads
Fault capacity (short
circuit)