EasyManua.ls Logo

ABB PCS100 UPS-I - PCS100 Inverter

ABB PCS100 UPS-I
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PCS100 UPS-I User Manual 35
5.1.7 PCS100 Inverter
The PCS100 Inverter modules are IGBT based power electronics modules rated at 150 kVA.
The inverters include a sine filter as part of the assembly, meaning the power electronics and sine filter are
integrated into one module.
Sine Filter
Fuses
IGBT
RFI
Filter
U
V
W
+ Bus
- Bus
SCR/Contactor
BYPASS
Fuses
Figure 5-7: PCS100 UPS-I inverter diagram
Figure 5-8: PCS100 Inverter
In addition to converting DC storage voltage to AC voltage required by the load, the inverters quickly re-charge
the energy storage (fast charging) after a power quality event.
Depending on the required power, between one and twenty ABB PCS100 inverters are used.
Each inverter module has a unique identification number (1 - 32) which is displayed on the front of the module.
The inverter cooling fans are switched off most of the time. They switch on when the PCS100 UPS-I is discharging
and remain switched on for about 30 seconds afterwards.
The cooling air flow is 9 m
3
/min per inverter module.
Advanced Redundancy
The PCS100 UPS-I inverter consists of multiple 150 kVA PCS100 Inverter modules connected in parallel. If one
module fails the PCS100 UPS-I will automatically reconfigure during stand-by or while supporting the load to
operate with the remaining modules.
For example, a six inverter PCS100 UPS-I system offers 900 kVA for normal load protection. If one module fails,
the maximum system capacity will be reduced to 750 kVA, and the PCS100 UPS-I GDM (HMI) will indicate system
availability of 83%.
A maximum of 50% of the modules can fail before the PCS100 UPS-I will trip out.

Table of Contents

Related product manuals