92 PCS100 UPS-I User Manual
10.3.8 Menu 700 Charger Settings
Sets which chargers will operate
None, Float, Module, Both
Sets the current level during charging
% of the PCS100 UPS-I rated current
10% for battery systems, 20% for Ultracapacitors
Because charging feeds power into the energy storage (Ultracapacitors or batteries)
which have low impedance the inverters are current controlled and the accuracy of the
current may be reduced.
715 Force Float Charger On
Forces the Float Charger on.
This should only be used to assist maintenance work, such as when measuring battery
balance or reconnecting a discharged capacitor enclosure.
Table 10-9: Menu 700 Charger Settings